系统背景
System Background
Compressor control system network is a Ring network composed of a pair of redundant controllers, 2 IO racks and other devices.
压缩机控制系统是由一对冗余控制器、两个IO机架以及其他设备构成的环形控制网络。
The communication link from the CPU to IO Rack is redundant.
控制器与IO机架之间的通讯是冗余的。
问题陈述
Problem Statement
Rack-2 all the modules show abnormal status.
2号机架所有模块状态异常。
Re-power the Rack-2, modules could not resume work.
重新上电状态不能恢复。
调查发现
Findings
Ping Rack-2 IP Address (192.168.7.72) failed.
2号机架IP地址(192.168.7.72)Ping 不通。
RSlinx also could not recognize.
使用RSlinx 同样识别不到该机架。
采取措施
Action taken
Remove the first “AENTR” module to check the MAC address of the Rack-2.
拆除机架最左侧第一块“AENTR”模块,查看机架MAC 地址。
Laptop connects to network switch, and set the IP address in range of the control network.
笔记本电脑链接至网络交换机,设置同网段IP地址。
Open the “BootP DHCP EtherNet/IP Commissioning Tool” software; the scan job will carry out automatically.
打开“BootP DHCP EtherNet/IP Commissioning Tool”软件,自动搜索。
Double-click the device (MAC address matching the Hardware label) to set an IP address.
双击设备(与硬件标签相匹配的MAC地址)设定IP地址。
Select the device from the menu below and hit the “Disable BOOTP/DHCP” button.
在下方列表选中设定好IP地址的设备,然后点击“Disable BOOTP/DHCP”。
Note注意:
This step is very important, after pressed, the message must be showed as“[Disable BOOTP] Command successful”
这一步非常重要,点击之后,一定要在下方信息栏看到“[Disable BOOTP] Command successful”命令发送成功的信息提示
Otherwise, the IP address configuration will be lost in any powered down.
否则设备会在断电后丢失之前设定的IP地址。
Sometimes, the message not come or receive a fault message, should try more times or change to use the other way to “Disable BOOTP/DHCP” as below:
有时,点击后会出现没有信息提示或者返回报错信息,这个时候就要多试几次,或者使用其他方式发送“Disable BOOTP/DHCP”命令,如下:
● Select the device → Menu Bar → Tools →“Disable BOOTP/DHCP”
选择设备 → 菜单栏 → Tools →“Disable BOOTP/DHCP”
●Select the device → right click → “Disable BOOTP/DHCP”
选择设备 → 右键 →“Disable BOOTP/DHCP”
处理结果
Result Status
Rack-2 status is back to normal.
机架、模块状态恢复正常。